Building |
|
|
Total
Size |
|
303,000 square feet
footprint 376,000 Square feet total Enclosed space |
Construction |
|
Tilt-up concrete structure with
reinforced steel. Dual reinforced roof. |
Total Raised
Floor |
|
168,000 Sq Ft of 48” raised
floor. All raised floor will support 6000 lb four-point
load. |
|
|
|
Communications |
|
|
Carriers |
|
Diverse SONet Fiber access from
ITC^DeltaCom and Bell South. Internet access from InterNap and ITC^DeltaCom,
providing peering with more than 10 Tier I Backbones. |
Internal
Cabling |
|
Copper and fiber access to
carrier bandwidth using cable management trays throughout
building. |
External
Cabling |
|
Multiple secure entrances into
building including multiple CO redundancy and fiber access to primary
carriers. |
|
|
|
Power |
|
|
Power to
facility |
|
Dedicated redundant feeds from
local power company. |
Generated
Power |
|
Critical Power
– Six HiTec flywheel generators (1.8 mva each) provide conditioned UPS power for
the data center floor without the need for batteries.
Non-Critical
Power – six Diesel Generator (2 mw) backup non-critical systems such as
chiller plant, office space, etc.
Fuel - 78,000
gallons capacity of diesel fuel on site with refueling contracts. 4 days at max.
load |
Power
Cabling |
|
All power cabling below floors
is encased in waterproof conduit with waterproof connectors to all
equipment. |
All
Systems |
|
Supported by 24/7/365 computer
monitoring and facility engineers. |
Cooling |
|
|
Air
Handling |
|
N+1 Chiller plant Redundant
piping systems for chilled fluid. Generator Backup for cooling system is
provide by 6 CAT 2.0 mw Generators |
Air
Quality |
|
Air temperature under floor
delivered at 68° ± 5° with humidity at 50% ± 5%. |
Water
Detection |
|
Leak detection under all raised
floor. Drains are utilized to remove any water from under
floor. |
|
|
|
Fire
Protection |
|
|
Smoke & Heat
detection |
|
Smoke sensors above and below
raised floor. |
VESDA |
|
Very Early Smoke Detection
Apparatus -the world’s leading air sampling smoke detection system—provides the
earliest possible warning of a potential fire event by detecting smoke particles
at the incipient (first) stage of fire. |
Multi-Stage
Protection |
|
Preaction dry pipe system
requires alert from two sensors, which activates pipe fill and a final stage
when the temperature exceeds thresholds. |
|
|
|
Physical
Security |
|
|
Entrances |
|
All building entrances require
card key access. Data Center floor and secured areas require card key and two-
factor biometric authentication (finger print and iris
scan). |
Security
Guards |
|
Guards on site 24/7/365. Active
patrols both inside and outside the facility. |
Closed Circuit
Video |
|
Over 70 cameras cover inside and
exterior of building, all entrances, alternate workspace, and data center
floor. |
|
|
|
Facility
Monitoring |
|
|
Facility
Engineers |
|
Facility engineers on site and trained to control and maintain all critical
facility components. |
Power
Management |
|
Critical power system controlled
by automated management system, which controls all switching.
|
Environment
Management |
|
Air temperature, humidity, fire
detection, and water pressure all managed by automated control
systems.
|